The STO Function can be used for disabling the energy to the motor. The motor will thereby be set in a state where it produces no torque.
The STO function has its own input connector mounted at the front of the motor.
It is a two input system and it is required that both inputs are activated (applied with a voltage) before the motor is energized and can operate normally.
The STO is available for all ServoStep products.
To read more about MAC STO, click here.
| Parameter | Value |
|---|---|
| Safety standards | IEC 61508-1:2010, IEC 61508-2:2010, IEC 61800-5-2:2016, IEC 62061:2015, ISO 13849-1:2015, ISO 13849-2:2012 |
| SIL/SILCL | 3 |
| PL | E |
| SFF (%) | 96 |
| PFHd (1/h) | 1.38e-10 |
| MTTFd (yrs/channel) | 854 |
| DC (%) | 96 |
| Cat. | 3 |
| SC | 3 |
| HFT | 1 |
| CCF | 75 |
| Lifetime (yrs) | 20 |
Why MIxyyz written on the Safety approved?
This is just a general short type code to the describe the whole range, so this certification covers a lot of different type numbers:
x = S,L (S=Rotary movement, traditional stepper MIS range and L=Linear actuator MIL range)
yy=17,23,34,43 (defines the motor flange size)
z = 0,1,2,3,4,5,6 (defines the maximum torque)
| Partnumber | Motor | STO Connector |
| MIS17xQ/R/S/T MIL17xQ/R/S/T User Manual | ![]() ![]() | |
| MIS23x/Q/R/S/T User Manual | ![]() | |
| MIS34x, MIL34x User Manual | ![]() | |
| MIS43x User Manual | ![]() | ![]() |
| SMC66x Available with STO connector. The STO function is not yet approved by TUV but use same components as MIS17x and MIS23x that are TUV approved. User Manual | ![]() | |
| SMC85x Under development. Please contact JVL. Available with STO connector. The STO function is not yet approved by TUV but use same components as MIS34x that are TUV approved. Please notice only foot mount possible (DIN mounting not possible) User Manual | ![]() |
Accessories:
Disabling the STO function (NON-STO plug)
If the STO function is not needed the plug JVL type WI1010-M08M4SSTO must be inserted in the STO connector.
The need of this external plug to disable the STO function is to obtain a high safety level and make sure that no misunderstandings will occur concerning whether the STO function is active or not.
Part number: **WI1010-M08M4SSTO**
Standard cable
The standard cable is mandatory to use in applications where the TÜV approval is required.
Part number: WI1010-M08M4V05P
How to connect and use the STO function:
The STO connector contains the two enable inputs STOA and STOB. Both inputs must be applied nominal +24 VDC in order to energize the motor and make any motor movement possible.
If only one of the inputs is not applied +24 VDC the internal STO circuit will remove the energy from the motor. Please note: In a SIL3/PLe application, both channels must be controlled simultaneously.
The illustration below shows the pinout of the connector
Ordering information:
ServoStep motors with the STO function installed are identified in the last two digits of the type number as seen below:
- EN ISO 13849-1/2
- EN IEC 62061
- EN IEC 61800-5-2
- EN 61000-6-3
- EN 61800-3
- EN 61800-5-1
- EN ISO 13849-1/2, IEC 62061, IEC 60204-1
- IEC 61508-1/2, IEC 61800-5-2
- Safe Torque Off (STO) - Stop Category 0
- Input to output response time
- Maximum 8 ms.
- Response time (internal fault)
- Maximum 200 ms.
- Category
- Cat 3
- Diagnostic Coverage
- DCavg: 98.5 % (Medium)
- MTTFd (per channel)
- 100 years (High)
- PFHd
- 4.29e-8/h
- Performance Level
- PLe
- Safety Integrity Level
- SIL 3, SIL CL3
- PFHd (High Demand Mode)
- 1.38e-10/h
- Diagnostic Coverage
- DC: 96 %
- Safe Failure Fraction
- SFF: 96 %
- Common Cause Failure Factor
- CCF 5 %
- Hardware Fault Tolerance
- HFT: 1 (1oo2)
- Proof Test Interval T1
- 20 Years
- Mission time TM
- 20 Years
SISTEMA:
The SISTEMA software utility provides developers and testers of safety-related machine controls with comprehensive support in the evaluation of safety in the context of EN ISO 13849-1.
For more information or to download the tool for free visit the website of the IFA.
Many companies use the SISTEMA libraries when designing a machine with several safety components. JVL offers for particular technologies continuously growing SISTEMA-Libraries. The libraries can be used with SISTEMA starting from version 1.1.1. Download the tool here Link to SISTEMA Library.
Your advantages:
- Fast calculation of the Performance Level
- Easy and fast access to safety relevant data
- Data for certified and standard components
- The tool is supported by many manufacturers
Link to Downloads - STO & SISTEMA files.
Link to preliminary safety manual. (see latest in user manual)